Five minutes, no tools, and it catches the failure that floods basements. The monthly check for a float switch, plus the alarm test that has to be done separately.
A float switch is the cheapest component in a lifting station and the most likely to stop the station working. It fails mechanically — it sticks, tangles or rests against a wall — and it gives no warning when it does.
Five minutes a month is enough to catch it. This is the procedure, and the part most people skip.
Before you start
| Check | Why |
|---|---|
| You know where the isolator is | You will need it if the pump does not stop |
| You can hear the pump from where you are standing | Listening is the fastest test |
| The tank is not already at alarm level | If it is, deal with that first |
| Nobody is using the fixtures served | So the level does not change under you |
Do not put your hand into a tank. Everything below is done from outside, with the lid open, using the float's own cable or a lifting hook.
The three-part test
Part 1: Does it start the pump?
- With the pump off and the tank at rest, note the level.
- Lift the float by its cable — gently, not by the body.
- The pump should start as the float reaches its switching angle.
If it does not start, the float, the cable or the control circuit has failed. Stop here and investigate.
Part 2: Does it stop the pump?
- Hold the float up until the pump has run.
- Lower it slowly back to its resting position.
- The pump should stop at the switching angle.
If the pump runs on, either the float has not returned to the "off" angle, or the contact is stuck closed. A pump that will not stop will overheat and eventually trip.
Part 3: Does it return freely?
- With the pump off, lift the float and let it go.
- It should fall back to its rest position on its own, without help.
If it hangs, it is fouled or it is resting against something. This is the failure that causes "pump never runs" faults, and it is invisible until the tank overflows.
What each result means
| Result | Likely cause | Action |
|---|---|---|
| Will not start | Float stuck down, cable damaged, contact failed | Free it, check cable continuity, replace if needed |
| Will not stop | Float stuck up, contact welded, level still high | Free it, replace if contact is welded |
| Does not return freely | Tangled on cable, resting on wall, fouled with grease | Reposition, fit a guide, clean |
| Starts and stops rapidly | Switching band too narrow | Reset the tether length |
| Works, but alarm also sounds | Alarm level set below start level | Reset the alarm higher |
The part everyone skips: testing the alarm
The float that runs the pump is the component most likely to fail. If the high-level alarm shares that float, the alarm fails at the same moment as the pump — which is exactly when you need it.
So the alarm must be tested on its own, not by lifting the duty float.
| Alarm type | How to test it |
|---|---|
| Separate float | Lift the alarm float by its cable; the alarm should sound |
| Test button on the panel | Press and hold; the alarm should sound and the beacon should light |
| Probe-based | Use the controller's test function; do not bridge terminals by hand |
What you are testing: that the alarm makes a noise you can hear from inside the building, and that any remote dialler or app notification actually arrives.
A common finding: the alarm sounds, but nobody in the house can hear it from the kitchen. That is a failed test even though the device worked.
Monthly record
Keep it simple. Four columns, one line per month.
| Month | Start test | Stop test | Returns freely | Alarm heard from living area |
|---|---|---|---|---|
| Jan | Pass | Pass | Pass | Yes |
| Feb | Pass | Fail — pump ran on | Pass | Yes |
| Mar | Replaced float | Pass | Pass | Yes |
The value is in the pattern. Two failures in three months means the position is wrong, not the float — and repositioning is cheaper than replacing a float every quarter.
When to replace rather than adjust
| Symptom | Adjust or replace? |
|---|---|
| Float rests against the tank wall | Adjust — fit a guide or bracket |
| Float tangles on the pump cable | Adjust — re-route the cable, fit a cable tidy |
| Switching band too narrow | Adjust — change tether length |
| Float does not tilt even when free | Replace — the internal ball has failed |
| Cable insulation cracked or stiff | Replace — water will enter |
| Contact welded closed | Replace — the switch is finished |
| Float body swollen or deformed | Replace — the material has degraded |
Floats are inexpensive. Replacing one that shows any of the last four signs is cheaper than the flood it prevents.
The annual version of this test
Once a year, do the monthly test plus:
- Check the cable along its whole length for nicks, stiffness or chafing at the gland.
- Clean the float body — grease and sludge change its buoyancy.
- Confirm the alarm level is still above the pump start level, especially if anything has been adjusted during the year.
- Confirm the alarm still reaches whoever needs to know, including any remote notification.
- Check the float is still the right height relative to the pump's stop level — a float that lets the pump run dry is worse than one that fails.
Working on a real project?
Send the fixture list, not the model code
Send the fixture list, required lift height and supply voltage. We will recommend the matching model from the 2026 catalog.
FAQ
How often should a float switch be tested? Monthly for the start/stop function, and the alarm tested separately at the same time. Annually, add the cable and body inspection.
Can I test the float without opening the tank? On some stations, yes — if the float cable is accessible above the lid. If not, the lid has to come off. Do not reach into the tank; use the cable or a hook.
My float passes the test but the pump still fails sometimes. Why? Intermittent failure usually means the float occasionally rests against something and only sticks sometimes. Watch it through a full cycle, or fit a guide so its position is fixed.
Should I replace the float as a precaution? Not on a schedule. Replace on the signs above. A float that passes all three tests and returns freely is doing its job.
Next step
Tell us the station arrangement and the control type, and we will confirm how the float should be positioned, what switching band to set, and how the high-level alarm can be kept on an independent device so a single failure cannot disable both.
Request a quotation · How to set float switch height · See the range
Related reading
- How to set float switch height — the setting this test protects
- Float switch stuck: symptoms and repair — when the test fails
- Float switch vs pressure switch vs electronic control — a design with nothing to tangle
- How to fit a high level alarm — keeping it independent
- Sewage lifting station maintenance schedule — where this fits in the year
Still unsure? Message the engineer on WhatsApp.