The high-level alarm is the only component that warns you before a flood. Where to set the float, which sensor type to use, how to wire it and how to prove it works.
A high-level alarm is the only component on a lifting station whose job is to warn you before something goes wrong. Every other part works silently until it fails. The alarm is the one that speaks up.
That makes it the highest-value item you can add to a station, and the one most often left out because the station "works fine without it". It works fine until the day the pump jams on a Saturday evening, and the difference between a five-minute callout and a flooded basement is whether anyone knew in time.
Where the alarm float goes
Three constraints, and the float has to satisfy all of them:
| Constraint | Reason |
|---|---|
| Above the start level | Otherwise it alarms on every normal cycle |
| Below the inlet | An alarm that fires only after the tank overflows is not an alarm |
| Clear of the inflow and the foam | Splash and suds produce false trips |
The usual setting is 100–150 mm above the start level. That is enough that the pump has a chance to respond, and low enough that there is still volume left before the inlet.
If the gap between the start level and the inlet is too small for a sensible margin, the tank is undersized for the duty — which is itself worth knowing.
Float heights in general are covered in how to set float switch height.
Which sensor type
| Type | How it works | Strengths | Weaknesses |
|---|---|---|---|
| Float switch | A buoyant body rises and closes a contact | Cheap, simple, no power at the sensor, easy to test by hand | Moving part; can foul, stick or fill with water |
| Conductive probe | Two electrodes sense water bridging them | No moving parts, compact | Needs conductive liquid; fouling causes false or missed alarms; grease coats the probes |
| Pressure transducer | Senses the hydrostatic head | No moving parts in the tank, continuous level reading | Needs power and a controller; more expensive |
| Ultrasonic | Measures the distance to the surface | Non-contact, nothing in the sewage | Costly; foam and condensation interfere |
For a domestic or light commercial station, a float switch is the right answer. It is inexpensive, it needs no power in the tank, and — critically — you can test it by lifting it by hand once a month.
A float's main failure mode is sticking. That is a known, testable failure, which makes it safer than a sensor whose failure is invisible.
Wiring
| Point | Requirement |
|---|---|
| Separate cable from the pump float | Never share a cable or a gland; a fault in one takes out both |
| Own circuit or own terminals in the panel | The alarm must be identifiable and testable on its own |
| Battery backup | A power failure is itself an alarm condition; the alarm must work when the supply does not |
| Volt-free contact for remote signalling | Allows connection to a dialler, BMS or building alarm without modification |
| Cable gland sealed | A gland that lets water in will fail the float |
| Labelled at both ends | "High level alarm — tank 1", not "spare" |
Battery backup is not optional. The most common genuine alarm condition is a power cut, because a pump with no power cannot pump. An alarm that dies with the supply is silent exactly when it matters.
Output: where the alarm should be heard
The alarm in the tank chamber is nearly useless. Nobody is in the chamber. The question is who hears it.
| Output | Where it works |
|---|---|
| Local sounder on the panel | Only if the panel is in an occupied, staffed space |
| Repeater sounder in a corridor or reception | Domestic buildings, small commercial |
| Dial-out / SMS / app notification | Unattended sites, holiday lets, remote plant rooms |
| Volt-free contact to a BMS | Managed buildings with a monitoring system |
| Strobe or beacon | Noisy plant rooms where a sounder is inaudible |
For a building with no staff on site, a local sounder alone is not an alarm system. It is a device that makes a noise in an empty room.
Step by step
- Isolate the power and confirm the station cannot start.
- Measure the start level — the level at which the pump starts — and mark it.
- Mark the alarm level 100–150 mm above it, and confirm it is below the inlet.
- Fit the float on its own bracket or cable, free to travel through its full range, clear of pipework, the pump cable and the inflow.
- Set the counterweight or tether length so the float switches at the marked level, not higher or lower.
- Run the cable in conduit where it passes through the chamber, with a drip loop before the gland.
- Wire to the panel on its own terminals, with battery backup.
- Connect the output — sounder, dialler, BMS or all three.
- Label everything at both ends.
- Test by lifting the float by hand and confirm the alarm sounds and any remote signal is received.
- Test the battery backup by switching off the supply and confirming the alarm still responds.
Testing, and how often
| Test | Method | Interval |
|---|---|---|
| Float free | Lift and release; it should fall back under its own weight | Monthly |
| Alarm sounds | Lift the float to its switching point | Monthly |
| Remote signal | Confirm the dialler or BMS receives it | Quarterly |
| Battery backup | Switch off the supply and repeat the alarm test | Quarterly |
| Cable and gland | Inspect for water ingress and corrosion | Annually |
| Float body | Shake it — water inside means replacement | Annually |
The monthly test takes a minute. It is the single highest-value maintenance action on the whole station, because it is the only one that tests the thing that tells you about all the others.
Avoiding false alarms
A high-level alarm that cries wolf gets disconnected, and a disconnected alarm is worse than none because it creates false confidence.
| Cause of false alarm | Fix |
|---|---|
| Float set too low | Raise to 100–150 mm above start level |
| Float in the inflow splash | Move it away from the inlet, or fit a shield |
| Foam lifting the float | Reduce detergent load; check the trap is not passing suds |
| Float fouled on pipework | Reposition; add a guide if the tank is crowded |
| Water inside the float body | Replace the float — a flooded float sinks and never alarms |
| Corroded terminals in a damp chamber | Re-terminate, seal the gland, use a junction box outside the chamber |
| Latching alarm not reset | Check the panel's reset function, not the float |
Note the last two: one causes false alarms, the other causes missed alarms. A float full of water is the more dangerous of the two, because the station looks protected and is not.
When the alarm sounds
Write the response down and put it next to the panel.
- Look in the tank. Is the level actually high?
- If high — stop using the fixtures served by the station.
- Check whether the pump is running. If not, check the power, then the float, then the pump.
- If the level is normal — it is a nuisance alarm; log it and get the float or wiring checked.
- Do not silence and leave.
The full diagnostic path is in lifting station alarm keeps sounding.
Working on a real project?
Send the fixture list, not the model code
Send the fixture list, required lift height and supply voltage. We will recommend the matching model from the 2026 catalog.
FAQ
Where should the high-level alarm float be set? 100–150 mm above the pump's start level, and always below the tank inlet. Any lower and it alarms on normal cycles; any higher and it fires too late to prevent a flood.
Can I use the pump's own float for the alarm? No. The alarm needs its own float on its own cable and its own terminals, so that a fault in one does not disable the other.
Does the alarm need battery backup? Yes. A power failure is one of the most common reasons a pump stops, so an alarm that dies with the supply fails exactly when it is needed.
How often should I test it? Monthly, by lifting the float by hand. Quarterly, test the remote signal and the battery backup.
Next step
If you are adding an alarm to an existing station, send the model code and the panel arrangement. We will confirm a float that suits the tank and the level range you need.
Request a quotation · Alarm keeps sounding · See the range
Related reading
- How to set float switch height — the start and stop levels the alarm float is set relative to
- Float switch stuck — the failure mode a monthly lift test catches
- Sewage lifting station maintenance schedule — where the alarm test belongs
Still unsure? Message the engineer on WhatsApp.