A stuck float either floods the room or burns out the pump. Identify the failure mode by symptom, test it in two minutes, and know when to replace.
A stuck float switch fails in one of two directions, and the two consequences are opposite. Stuck down means the pump never starts and the tank overflows. Stuck up means the pump never stops and runs until it destroys its own seal or trips the overload. Both are common, both are cheap to fix, and both are frequently misdiagnosed as pump failure.
The float is the most frequently replaced component on a external lifting station — not because it is poorly made, but because it is the part that touches everything: the wastewater, the debris, and the person who last opened the lid.
Identify the failure mode first
| Symptom | Failure mode | Consequence if left |
|---|---|---|
| Tank fills, pump never starts | Float stuck down, or contacts open | Overflow |
| Pump runs continuously | Float stuck up, or contacts welded | Dry running, seal failure, overload trip |
| Pump starts and stops erratically | Float fouling something, or water inside the float | Short cycling |
| Pump starts late, tank nearly full | Float travel restricted | Reduced buffer, occasional overflow |
Establishing which of these you have tells you where to look before you open anything.
The two-minute test
Isolate the power, open the lid, and lift the float by hand through its full travel.
| Observation | Meaning |
|---|---|
| Audible click, pump starts when power restored | Switch is working — the problem is elsewhere |
| No click at all | Switch has failed mechanically or electrically |
| Click but pump does not run | Switch is fine; fault is downstream (contactor, capacitor, motor) |
| Float does not hang freely | Fouling on the inlet pipe, cable or debris |
| Float sits low in the water, not on the surface | Water inside the float body |
That last observation is worth checking carefully. A float with a split cable sheath fills with water, loses buoyancy and sits submerged — it never rises far enough to trip, and it looks perfectly normal from above.
Cause 1: Fouling on the inlet pipe or debris
The most common cause by a wide margin. A tethered float hangs in the tank and will tangle with anything within reach: the inlet pipe, the discharge pipe, a cable, or a mass of wipes.
Signs: float visibly displaced to one side; erratic switching; float trapped under the inlet.
Fix: free the float and reposition the tether anchor so the float hangs in clear water. If the tank geometry makes fouling inevitable, a vertical guided float or a different mounting point removes the problem permanently.
Prevention: check the float hangs free at every service. This takes seconds and prevents most call-outs.
Cause 2: Water inside the float body
A tethered float is a sealed hollow body. A crack, or a split in the cable sheath where it enters the body, lets water in. The float loses buoyancy and behaves unpredictably — sometimes rising enough to trip, sometimes not.
Signs: float sits lower than it should; the switching level varies between cycles; water can sometimes be heard inside when the float is shaken.
Fix: replace the float. There is no reliable repair for a water-filled float body.
Prevention: route the cable so it is not flexed sharply at the entry point, and avoid leaving the float resting on debris.
Cause 3: Contacts welded or worn
Inside the float is a microswitch. Repeated switching, or switching a motor with a high inrush current directly, wears the contacts.
Signs: pump runs continuously (contacts welded closed), or pump never runs despite the float moving (contacts burned open).
Fix: replace the switch. On most stations the float is a replaceable item and is inexpensive relative to the pump it protects.
Prevention: where a station switches the pump directly through the float, the float carries the full motor current. Stations that use a contactor in a control panel impose far less load on the float and last longer. If you are specifying, that is a reason to prefer a controlled station over a direct-switched one.
Cause 4: Cable damage
The float cable flexes every cycle. Over years, the conductor strands break inside intact-looking insulation.
Signs: intermittent operation that becomes more frequent; operation changes when the cable is moved; continuity test fails intermittently.
Fix: replace the float and its cable. Do not splice a float cable — the joint will be in the wastewater.
Prevention: ensure the cable has enough slack to move through its full travel without tension, and that it is not rubbing on a sharp edge.
Cause 5: Mechanical obstruction in the tank
A float can be held down by something heavy resting on it — a piece of debris, a collapsed inlet grommet, a fallen lid gasket.
Signs: pump never starts; float appears submerged under debris.
Fix: clear the obstruction and clean the tank. If debris is reaching the tank in quantity, the upstream problem matters more than the float.
Testing with a multimeter
If the visual check is inconclusive, test electrically.
- Isolate the power and disconnect the float from the circuit.
- Set the meter to continuity or resistance.
- With the float hanging down (empty position), read the contacts.
- Lift the float to the raised position and read again.
A working switch changes state cleanly — continuity in one position, open circuit in the other. A switch that reads the same in both positions, or that reads intermittently as the float is moved, has failed.
Some floats are normally-open and some normally-closed depending on whether they switch the pump on or off. Know which type you have before concluding from the reading.
Replace or repair?
| Fault | Repair or replace |
|---|---|
| Fouling | Repair — free and reposition |
| Water in the body | Replace |
| Welded or worn contacts | Replace |
| Cable damage | Replace |
| Wrong setting (levels) | Adjust, do not replace |
| Switch working but pump not running | Neither — the fault is downstream |
The general rule: a float is a consumable and costs a fraction of a pump. Replacing a suspect float is almost always cheaper than the second visit to diagnose a pump that was never at fault.
Prevention
| Action | Interval |
|---|---|
| Lift the float by hand and confirm the pump starts | Monthly |
| Check the float hangs free of the inlet pipe | Monthly |
| Inspect the cable for cracks at the entry point | Every service |
| Clean debris from the tank | Annually, or as the waste load requires |
| Replace the float after any water ingress | Immediately |
A monthly hand-lift takes under a minute and catches the majority of float failures before they become an overflow.
When it is not the float
If the float tests correctly and the pump still will not run, the fault is downstream: contactor, capacitor, overload, winding or supply. Our guide to sewage pump not starting sets out the diagnostic order.
If the pump runs but the tank keeps refilling, the float is fine and the non-return valve is passing.
Working on a real project?
Send the fixture list, not the model code
Send the fixture list, required lift height and supply voltage. We will recommend the matching model from the 2026 catalog.
FAQ
How often should a float switch be replaced? There is no fixed interval — replace on failure. In a heavily used station, a float may last several years; in a lightly used one, longer. The monthly hand-lift test tells you when it is degrading.
Can I bypass the float to test the pump? Only momentarily and only with the tank wet. Running a sewage pump dry, even briefly, damages the seal. A safer test is to lift the float by hand rather than bypassing the circuit.
Why does my pump run all the time? Most often a float stuck in the raised position or with welded contacts. Isolate the power and lift the float by hand; if the pump keeps running with the float down, the switch has failed closed.
Is a vertical float better than a tethered one? A vertical guided float cannot tangle with pipework, which makes it more reliable in tanks with obstructions. A tethered float is simpler and cheaper. In a clean tank either works.