Where to Fit the Non-Return Valve on a Sewage Lifting Station

2026-11-025 min readInstallation and Commissioning

Position, orientation and accessibility decide whether a non-return valve protects the station or becomes the fault you cannot reach. Here is where it belongs.

The non-return valve goes on the discharge line, immediately above the pump and above the tank's maximum water level, in a position that stays accessible for service. Its arrow must point away from the pump. Fitted anywhere else — inside the tank, below the lid in a sealed floor box, or downstream of the first bend — it will work for a while and then become a fault you cannot reach without cutting pipework.

This is a small component that decides whether a station behaves well or short-cycles for years. It is worth getting right the first time, because relocating one later is a demolition job.


What the valve is doing

A non-return valve (also called a check valve) allows flow in one direction only. On a lifting station it does two jobs:

1. It holds the pumped column. When the pump stops, the water in the vertical discharge pipe wants to fall back into the tank. Without a valve, it does, and the pump restarts almost immediately — this is short cycling, and it will wear out a motor and a float switch long before their time.

2. It stops backflow from the sewer. Where the discharge connects to a shared stack, the valve prevents anything from the sewer travelling back down into the station. Without it, sewer gas and, in a blockage, sewage itself can enter the tank.

Both jobs require the valve to seal properly. A valve that is correctly placed but has a worn seat does neither.


The correct position

RequirementWhy
On the discharge line, not the inletThe inlet is gravity-fed; a valve there would block incoming wastewater
Above the pumpProtects the pump from the falling column
Above the tank's maximum water levelKeeps the valve out of the wastewater, where solids foul the seat
Accessible for serviceIt will need cleaning and eventually replacing
Arrow pointing away from the pumpReversed, it blocks the flow entirely
Preferably before the first bendEasier to service and less prone to debris lodging

The "above maximum water level" point is the one most often compromised. A valve fitted inside the tank, or in a floor box below the lid, sits in the waste stream — solids collect behind the flap and the seat never stays clean.


Vertical or horizontal?

Both orientations are available, and the choice depends on the pipe route.

Vertical (flow upwards). The flap closes by gravity plus the falling column, which gives the most reliable seal. This is the default where the discharge rises vertically from the station.

Horizontal. Works, but the flap relies on spring or on the reverse flow to close. Choose a valve designed for horizontal installation; a vertical-only valve fitted horizontally will not seal.

Check the valve body or datasheet for the permitted orientations before ordering. Fitting a vertical valve horizontally is a common installation error that shows up as a station that short-cycles.


Combine with an isolation valve

A non-return valve alone cannot be serviced while the line is under pressure. Fit an isolation valve immediately downstream of it, so the line can be shut off before the non-return valve is opened.

The pair, in order from the pump:

pump → isolation valve → non-return valve → discharge route

or, depending on the station's internal arrangement:

pump → non-return valve → isolation valve → discharge route

Either sequence works, provided both are accessible and the isolation valve can be closed with the line live. What does not work is a non-return valve with no means of isolation — servicing it means draining the whole discharge line.


Where not to fit it

Inside the tank. Some installers place the valve in the tank to keep it out of sight. It sits in wastewater, fouls quickly and is unreachable without opening the lid and reaching into the contents.

Under a finished floor. A valve in a sealed floor box is a valve that will never be serviced. When it fails — and it will — the repair involves breaking the floor.

Below the tank lid in a shallow chamber. Same problem as above, with the added issue that the valve may be below the maximum water level.

Downstream of several bends. Debris lodges at the first change of direction. Keep the valve before the bends if the geometry allows.

On a shared line without a dedicated isolation. If two stations discharge into one line, each needs its own non-return valve, or one station will pump into the other.


Common faults and what they look like

FaultSymptom
Flap held open by debrisPump short-cycles; tank refills after each cycle
Seat worn or scaledSlow drain-back; pump runs again a minute after stopping
Valve fitted backwardsPump runs, no flow, high current
Valve fitted horizontally when vertical-onlyPoor sealing; intermittent drain-back
Spring broken (spring-check type)Flap does not close; continuous drain-back
Valve seized shutPump runs against dead head; no flow at all

The first two are by far the most common, and both are fixed by cleaning or replacing the valve — provided it can be reached.


Commissioning check

After installation, before handing over:

  1. Confirm the arrow direction against the pump flow.
  2. Run one cycle and watch the tank. After the pump stops, the water level should stay put. If it rises, the valve is passing.
  3. Listen for the flap closing. A distinct click at pump stop is normal; silence suggests it is not seating.
  4. Confirm the isolation valve operates and can be closed without tools.
  5. Confirm the valve is reachable without removing fixed panels or breaking the floor.

That fourth and fifth point are the ones that get skipped, and they are the ones that matter in year three.


A note on the station's own valve

Some packaged stations include a non-return valve integrated into the discharge spigot or supplied loose with the unit. If yours does, check whether it is a serviceable type — a valve that can be opened and cleaned without cutting pipe is worth having, and one that cannot be is worth replacing at installation rather than at failure.

Our European Type and American Type compact ranges and the AT-S external station range are supplied with the connection set for each model; the parameter table on the model page states the port sizes so the discharge fittings can be specified in advance. For an example, see AT-C300A and AT-S50.


Working on a real project?

Send the fixture list, not the model code

Send the fixture list, required lift height and supply voltage. We will recommend the matching model from the 2026 catalog.

FAQ

Does a sewage lifting station need a non-return valve? Yes. Without one, the discharge column drains back after every cycle, causing short cycling, and sewer gas can travel back into the tank.

Can the non-return valve go inside the tank? It physically can, and it is a bad idea. It sits in wastewater, fouls quickly and cannot be serviced.

Should the non-return valve be before or after the isolation valve? Either, provided both are accessible and the isolation valve can be closed with the line under pressure. What matters is that both can be reached.

Why does my pump restart a minute after stopping? Almost always a non-return valve that is not sealing — debris on the seat, a worn flap, or a valve fitted in the wrong orientation.


Next step

If you are specifying a station, tell us the discharge route and the bore available. We will confirm the connection set and the valve arrangement for that model.

Request a quotation · See the model range

Still unsure? Message the engineer on WhatsApp.

Models referenced in this note