Start level, stop level and alarm level decide cycle length, dry-run risk and whether the tank backs up. How to set each one and test the result.
A float switch is set by three levels: the stop level, where the pump cuts out; the start level, where it cuts in; and the alarm level, where a high-level warning triggers. The stop level must keep the impeller submerged, the start level must sit below the inlet invert, and the gap between them must give a cycle long enough that the pump is not switching on and off continuously.
Those three constraints are easy to state and easy to break. Most short-cycling complaints and most premature seal failures trace back to float levels that were never properly set at commissioning.
The three levels
| Level | Constraint | What goes wrong if it is wrong |
|---|---|---|
| Stop level | High enough to keep the impeller submerged | Set too low: pump runs dry, seal and motor overheat |
| Start level | Below the inlet invert | Set too high: wastewater backs up into the inlet pipe before the pump starts |
| Alarm level | Above the start level with usable buffer | Set too close: alarm gives no warning time |
The working volume is the volume between start and stop. It determines the cycle length: bigger volume, longer cycles, fewer starts.
Setting the stop level
The pump must stop while there is still water covering the impeller. Running dry for even a short period destroys a mechanical seal, because the seal is cooled and lubricated by the pumped liquid.
Practical setting: position the stop level so the impeller remains fully submerged with some margin. If the manufacturer publishes a minimum submergence for the model, use that figure rather than estimating.
On a station where the pump sits in a sump at the base of the tank, this is straightforward. On a station where the impeller is close to the tank floor, the margin is small and the setting matters more.
Setting the start level
The start level must be below the inlet invert. If it is above, incoming wastewater fills the inlet pipe before the pump starts, and the pipe becomes a wet sump — which is exactly where solids settle and odour develops.
Practical setting: at least the pipe diameter below the inlet invert, so the incoming flow drops into the tank rather than filling the pipe.
The start level also determines how much the tank fills before pumping. Setting it high gives a longer cycle and a larger buffer against a surge; setting it low gives a smaller working volume and more frequent starts.
Setting the alarm level
The alarm level sits above the start level, with enough volume between them that a rising level gives someone time to respond before the tank overflows.
Practical setting: enough buffer for a realistic response time. In a building with staff on site, that might be tens of litres; in an unmanned plant room, more. What matters is that the alarm does not trigger only seconds before overflow.
If the station has no alarm, the start level itself is the only warning, and the margin between start level and overflow is the entire safety buffer. That is a reason to fit an alarm on any station in an unvisited space.
Adjusting the two common float types
Tethered float
A tethered float hangs from a fixed point on a flexible cable. The tether length sets the levels:
- Longer tether → wider travel → lower stop level and higher start level → bigger working volume.
- Shorter tether → narrower travel → higher stop level and lower start level → smaller working volume.
Adjust by moving the cable clamp on the tether, then test.
Vertical (guided) float
A vertical float slides on a stem with stop collars that set the switching points:
- The lower collar sets the stop level.
- The upper collar sets the start level.
- Move both together to shift the working band; move them apart to change the working volume.
Pressure or diaphragm switch
Adjusted by a screw or by tube length, depending on the design. Follow the manufacturer's instructions — the relationship between adjustment and level is not always linear, so adjust and measure rather than calculating.
Testing the setting
Set, then verify with water rather than by eye.
| Test | How | Pass |
|---|---|---|
| Start level | Fill slowly, watch the level at which the pump starts | Starts at the intended level, not before |
| Stop level | Watch the level at which the pump stops | Stops with the impeller still submerged |
| Cycle length | Time one complete cycle | Long enough that the pump is not switching repeatedly |
| Inlet clearance | Observe the inlet during fill | No backing up into the inlet pipe |
| Alarm | Fill past the start level | Alarm triggers with usable margin before overflow |
| Repeatability | Run three cycles | Same start and stop levels each time |
The repeatability test catches a float that is snagging on the inlet pipe or on debris — it will trip at a different level each cycle.
Short cycling: is it the float or the valve?
A pump that starts and stops repeatedly has one of two problems, and they are often confused.
| Symptom | Likely cause |
|---|---|
| Pump stops, then restarts within a minute without new inflow | Non-return valve passing — water drains back |
| Pump starts after every small flush, runs briefly | Working volume too small — float levels too close |
| Pump runs almost continuously | Inflow exceeds pump duty, or a fixture is running |
The distinguishing test is simple: watch the tank after the pump stops. If the level rises with no water coming in, the non-return valve is passing. If the level holds and the pump still restarts quickly, the float setting is the problem.
What good looks like
A well-set station:
- Starts with the tank visibly filling, not with every trickle.
- Runs long enough that the motor reaches working temperature rather than repeatedly starting cold.
- Stops with water still covering the impeller.
- Holds its level after stopping.
- Alarms only when something is genuinely wrong.
That is a five-minute check at commissioning that prevents most of the service calls a station will otherwise generate.
Related reading
- Float switch stuck: symptoms and repair — when the float itself has failed rather than being mis-set.
- Where to fit the non-return valve — the other half of the short-cycling question.
- Sewage pump not starting — if the float is set correctly and the pump still will not run.
Our European Type, American Type and AT-S external station ranges all use float or pressure level control; the model page states the control type and the connection set for each unit.
Working on a real project?
Send the fixture list, not the model code
Send the fixture list, required lift height and supply voltage. We will recommend the matching model from the 2026 catalog.
FAQ
How do I know if my float switch is set too low? The pump stops while water is still visibly above the impeller, or the pump runs dry and becomes noisy. Set the stop level higher so the impeller stays submerged.
Why does my pump start every few minutes? Either the working volume is too small (float levels too close together) or the non-return valve is passing. Watch the tank after the pump stops to tell which.
Can I adjust the float without draining the tank? Usually yes, for a tethered or vertical float, provided the lid can be opened safely. Isolate the power first.
Does the float need to be off the bottom of the tank? The float should hang free and not rest on the tank floor or foul the inlet pipe. A float that touches anything will trip inconsistently.
Next step
If you are commissioning a station and the levels are unclear for your model, send the model code and the tank dimensions. We will confirm the control type and the recommended setting range.