Sewage Pump Cavitation: Causes and Fixes

2026-11-056 min readMaintenance and Troubleshooting

A noise like gravel in the discharge, falling flow, and pitted impellers. What cavitation is, why it happens on a lifting station, and how to stop it.

Cavitation is what happens when the pressure on the suction side of a pump falls below the vapour pressure of the liquid. Water boils at that pressure — not at 100 °C, but at whatever temperature it happens to be. Vapour bubbles form, get carried into the impeller, and collapse violently as the pressure rises again.

The collapse is the damage. Each bubble produces a micro-jet against the impeller surface, and thousands of them per second erode the metal. The sound is distinctive: like gravel or small stones passing through the pipe, not the usual hum.

On a domestic sewage pump, cavitation is less common than on industrial pumps, because the pump is submerged in a tank with the water right there. But it does happen, and it has a small set of causes that are all worth knowing.


What it sounds like, and how to be sure

SoundLikely cause
Gravel or stones in the dischargeCavitation
A rattle that stops when the pump stopsDebris in the impeller
A slurping or gurgling at the inletAir being drawn in — a vortex
A high-pitched whineBearing or seal, not cavitation
A thumping at regular intervalsA solid passing through, or a non-return valve

The distinction that matters most is between cavitation and air entrainment. Both produce noise and both reduce flow, and both can occur on the same station — but they have different causes and different fixes.

Cavitation is vapour forming because the pressure is too low. Air entrainment is actual air being sucked in because the water surface is too close to the pump inlet, or because the inlet pipe is drawing a vortex. The second is far more common on a lifting station, and the fix is a level setting rather than a hydraulic redesign.


The causes on a lifting station

1. The pump is running with the water level too low. This is the big one. As the level drops, the pump draws closer to the surface, a vortex forms, and air enters the impeller. Strictly this is air entrainment rather than cavitation, but the noise and the damage are similar enough that most people call it cavitation, and the fix is the same: raise the stop level.

A pump that pumps the chamber down to the impeller is running in air on every cycle. The seal is running dry, the impeller is being hammered, and the flow has already collapsed before the pump stops.

2. A blocked or restricted inlet. A strainer or inlet pipe partly blocked by debris raises the pressure drop across it, lowering the pressure at the pump inlet. On a gravity inlet this shows up as a tank that fills slowly; on a pump with a suction pipe it shows up as cavitation.

3. An inlet pipe that is too long or too small. Friction loss on the suction side reduces the pressure available at the impeller. A long, undersized suction run is a cavitation risk by design. Lifting stations usually avoid this by having the pump inside the tank, but pump-out or external arrangements can suffer from it.

4. Water that is warmer than expected. Warm water has a higher vapour pressure and cavitates more readily. A station receiving discharge from a commercial dishwasher, a laundry or a plant room can be running at temperatures the pump was not specified for.

5. A discharge that is partly blocked. This one is indirect but real: a restricted discharge reduces flow, which on some duty points moves the pump along its curve to a region where cavitation is more likely. It also raises the water temperature in the tank, compounding the problem.


What it does over time

Cavitation is not a nuisance noise. It removes material.

  • The impeller erodes, typically on the low-pressure side of the vanes, and the erosion looks like a rough, spongy surface rather than a clean wear pattern.
  • The head falls, gradually, as the vane profile changes. The pump still runs; it just produces less.
  • The seal suffers, because the vibration and the unstable load accelerate face wear.
  • The noise gets worse, and vibration can loosen fixings and pipework.

A pump that has been cavitating for a year will not be repairable by fitting a new impeller alone if the volute is also eroded — and by then the flow deficit is usually the reason someone is asking.


Fixing it

The fix follows the cause, and the causes are mostly cheap to address.

CauseFix
Stop level too lowRaise the float or sensor setting so the impeller stays submerged
Vortex at the inletSame — a higher level; sometimes a baffle or an anti-vortex plate
Blocked strainer or inletClear it, and check it on the maintenance schedule
Suction pipe too small or longIncrease the diameter, or shorten the run
Water too warmCheck what is being discharged into the station; the pump may be the wrong specification
Discharge restrictedClear the blockage; check the non-return valve is not stuck partly closed

The first row fixes most domestic cases and costs nothing. It is the same fix that prevents seal failure by dry running, which is why the two problems so often appear together — see Sewage pump mechanical seal failure.


Distinguishing it from a blockage

A blocked impeller and a cavitating pump both make noise and both reduce flow, and the treatments are opposite — one needs the pump opened, the other needs the level raised.

Three checks separate them:

  1. Does the noise stop when the level is high? Cavitation and air entrainment typically worsen as the level falls. A blockage is constant.
  2. Is the current high or low? A blockage usually raises current. Cavitation typically lowers it, because the pump is moving less mass.
  3. Does the flow recover if you stop and restart? A blockage does not clear itself. A cavitating pump often runs normally for the first few seconds of a cycle, before the level drops.

That third check is the most reliable one on a station where you can watch a full cycle.


Designing it out

For a new sewage pumping station, three decisions remove most of the risk:

Set the stop level on the pump, not on the tank floor. The impeller should stay submerged at the stop level. This single setting is the most common avoidable fault on domestic stations.

Give the tank enough working volume that the pump is not chasing a falling level in a small chamber. See How to choose tank volume.

Check what else discharges into the station. A commercial dishwasher or a laundry can raise the water temperature beyond what a domestic pump assumes, and warm water cavitates. The same caution applies to any sewage lifting unit fed by a kitchen or a plant room rather than by bathrooms alone.

None of these is expensive at design stage. All of them are awkward to change afterwards.


Working on a real project?

Send the fixture list, not the model code

Send the fixture list, required lift height and supply voltage. We will recommend the matching model from the 2026 catalog.

FAQ

Can a sewage pump cavitate if it is fully submerged? Yes, if the inlet is restricted or the water is warm enough. Submersion removes the most common cause — drawing air from the surface — but not all of them.

Does cavitation destroy a pump quickly? Not quickly, but steadily. It removes material from the impeller and the volute over months, and the pump's performance declines as it does. It is a slow failure that is easy to ignore until the flow is obviously wrong.

The noise only happens at the end of the cycle. Is that cavitation? That is the classic pattern for a stop level set too low: the pump is fine while the chamber is full and noisy as the level drops towards the impeller. Raising the stop level is the fix.

Is a noisy pump always cavitating? No. Debris, a worn bearing, a vibrating pipe and a non-return valve can all make noise. The gravel-like quality and the association with low level are what point at cavitation.


Next step

Tell us the tank volume, the stop level setting and when the noise occurs in the cycle, and we will tell you whether it is the level setting, the inlet or the duty — rather than assuming the pump is at fault.

Request a quotation · See the range · How to set float switch height