How to Choose Tank Volume for a Sewage Lifting Station

2026-11-025 min readSelection Guide

Tank volume is a buffer, and the number that matters is the working volume between start and stop. Too small short-cycles the pump; too large creates odour.

Tank volume is chosen so that the working volume — the amount between the pump's start level and its stop level — is large enough to absorb the peak inflow without making the pump start and stop repeatedly. The total tank volume is larger than the working volume, because the pump needs water covering the impeller at the bottom and the tank needs freeboard at the top.

Getting this wrong in one direction short-cycles the pump and burns out the motor. Getting it wrong in the other holds wastewater in the tank for too long, which produces odour and septicity.


Total volume versus working volume

These are not the same thing, and confusing them is the most common error.

VolumeWhat it isSet by
Total tank volumeThe whole internal capacityThe product
Working volumeBetween the stop level and the start levelThe float setting
Dead volume below stop levelKeeps the impeller submergedThe stop level position
Freeboard above start levelBuffer before the alarm and the inletThe start level position

A 90 litre tank might have a working volume of 40 litres, depending on how the float is set. The figure that governs pump cycling is the working volume, not the tank capacity on the datasheet.


What the working volume has to do

Two jobs.

1. Absorb the peak. When a bath empties or several fixtures run together, inflow can exceed the pump's capacity for a short period. The tank absorbs the difference. If it cannot, the level rises to the alarm or to the inlet.

2. Limit starts per hour. A motor has a maximum number of starts per hour, set by the manufacturer. Exceed it and the winding overheats, because starting current is several times running current and the heat has no time to dissipate between starts.

The working volume controls both. Bigger working volume means fewer starts and more buffer.


The sizing logic

The relationship is straightforward in principle:

  • The pump empties the working volume in a certain time.
  • Inflow refills it.
  • The cycle time is the sum of the fill time and the empty time.
  • Starts per hour is 3600 divided by the cycle time in seconds.

In practice, for a domestic installation, the useful approach is:

  1. Estimate peak inflow from the fixture group — see the fixture unit method.
  2. Check that the working volume holds at least several flush volumes. A WC flush is roughly 6 litres; a working volume that cannot hold three or four flushes will cycle on every use.
  3. Confirm the resulting starts per hour against the pump's limit.
  4. Check the peak absorption case — can the tank hold a bath emptying while the pump is running?

If any of those fails, the tank is too small for the application regardless of what the pump can do.


Indicative tank sizes by application

The table below gives the range that generally fits each application. It is a starting point, not a substitute for the calculation.

ApplicationTypical total tank volume
Single basement WCSmall — 25 L and upward
Full basement bathroomMid — 50–90 L
Bathroom plus washing machineMid to upper — 60–170 L
Multiple rooms, one stationUpper — 170 L and upward
Commercial or multi-dwellingExternal station — 170–460 L

Our AT-S external station range runs from 25 L to 460 L across six models, which covers that ladder. The compact ranges — European Type and American Type — use integrated tanks sized for a bathroom group.


Why too large is also wrong

The instinct is to specify the biggest tank available. That carries three costs.

Retention time. Wastewater sitting in a tank begins to turn septic. Long retention produces hydrogen sulphide and methane — which means odour, even with a correct vent, and increased corrosion of the tank and fittings.

Footprint and weight. A large tank full of wastewater is heavy and takes floor space. In a basement retrofit, neither is free.

Cost. Capacity that will never be used is capital and volume that buys nothing.

The right answer is a tank that buffers the peak and no more. On a domestic installation, that is usually the smaller end of the range.


The relationship to pump size

Tank volume and pump power solve different problems, and confusing them is how people oversize one and undersize the other.

If the problem is…The answer is…
Inflow arrives faster than the pump can move itA larger tank, to buffer
The pump cannot lift to the required headA larger pump, or a larger discharge bore
The pump short-cycles on small inflowsA larger working volume, or a higher stop level
The tank fills on every flushA larger working volume

A bigger pump does not fix a small tank. It empties it faster, which means it cycles more often.


Setting the levels after choosing the tank

Once the tank is chosen, the float settings determine the working volume within it:

  • Stop level — high enough to keep the impeller submerged.
  • Start level — below the inlet invert, so the inlet pipe does not become a wet sump.
  • Alarm level — above the start level, with enough buffer to respond.

For how to set these, see how to set the float switch height.


Working on a real project?

Send the fixture list, not the model code

Send the fixture list, required lift height and supply voltage. We will recommend the matching model from the 2026 catalog.

FAQ

What is working volume? The volume between the pump's start level and its stop level — the amount that actually gets pumped each cycle. It is smaller than the total tank volume.

How big should a tank be for a basement bathroom drainage? For a single bathroom group, a mid-range tank of roughly 50–90 litres is typical. The working volume within it should hold several flushes.

Can a tank be too large? Yes. Long retention time allows wastewater to turn septic, which causes odour and corrosion even with correct venting.

Does a bigger tank mean fewer pump starts? Yes, provided the float levels are set to use the extra volume. A larger tank with a small working volume setting behaves like a small tank.


Next step

Send the fixture list, the peak inflow you expect and the space available. We will confirm the tank volume and the model, with the parameter table for that unit.