How to Size a Duplex Sewage Pump Station

2026-11-056 min readSelection Guide

Each pump must carry the full duty, the tank must be larger than a single-pump version, and the alarm must sit above the both-pumps level. The calculation, step by step.

Sizing a duplex station is the same calculation as a single-pump station with three additions: each pump carries the whole duty, the working volume grows, and the alarm level moves up.

The mistake that causes most problems is treating the two pumps as a combined unit. They are not. One is working and one is spare, and the station has to perform on the working pump alone.

This article works through the six numbers you need, in the order that avoids rework.


Step 1: Establish the duty flow

The duty flow is the peak inflow the station must handle, not the average.

SourceHow to estimate it
Fixtures in the installationFixture units, converted to flow — the standard method
Known appliancesWashing machine, dishwasher, shower: manufacturer discharge figures
Tenanted or public buildingsPeak occupancy, not average occupancy
Grey water onlyLower peak, but check whether a washing machine is included

Two rules that matter more than the arithmetic:

  • Round up, not down. A station that is 10% oversized wastes a little energy; one that is 10% undersized runs continuously at peak.
  • Use the peak that actually happens. A single bathroom in a basement flat and a bathroom serving six tenants have the same fixtures and very different peaks.

Step 2: Establish the total head

Total head is static lift plus friction, and on a duplex station the friction is calculated for one discharge train, not two.

ComponentHow to get it
Static liftVertical height from the pump start level to the discharge point
Friction lossPer-metre loss for the pipe diameter and flow, times the developed length
FittingsBends, valves, non-return valve — each adds equivalent length
Discharge conditionFree discharge or into a pressurised sewer

The number you need is the head at the duty flow. Plot it on the curve: the duty point must sit comfortably inside the pump's operating range, not at the far right where efficiency falls away.


Step 3: Size each pump to the full duty

This is the step people get wrong.

Each pump must deliver the duty flow at the duty head on its own. If the station must move 12 m³/h at 6 m, both pumps are specified at 12 m³/h at 6 m — not 6 m³/h each.

What people specifyWhat it delivers
Two pumps at 50% of duty50% on one pump, 100% only while both run
Two pumps at 100% of duty100% on one pump, 200% briefly

The second is correct. The first is a station that works perfectly until the day it is needed.

The brief period when both pumps run is a bonus, not the design basis. It covers a genuine surge — a group of showers, a delivery to a commercial kitchen — but the station must not depend on it.


Step 4: Calculate the working volume

Working volume is the volume between the pump start level and the pump stop level. It exists to limit starts per hour.

The basic relationship:

Working volume ≥ (inflow per hour ÷ allowable starts per hour) × a safety factor

For duplex, two adjustments apply:

AdjustmentReason
Multiply the single-pump volume by roughly 1.3 to 1.5The station must hold inflow while the lead pump runs, the level falls, and the lag pump's start level is crossed
Set separate start levels for lead and lagTypically a small step between them, so the lag pump only cuts in on a real rise

Do not simply halve the volume because there are two pumps. The tank has to absorb the same inflow with more control levels packed into it, and squeezing the band causes both pumps to short-cycle — which is harder on the motors than a single pump cycling.


Step 5: Set the three levels

A duplex station has more levels than a single-pump one, and getting the order right is what makes it behave.

LevelFunctionTypical relationship
Stop levelBoth pumps offAbove the pump inlet, so neither runs dry
Lead pump startFirst pump onWorking volume above stop level
Lag pump startSecond pump onA step above lead start
High-level alarmWarningAbove the lag start, with the level still rising
Flood levelEmergencyAbove alarm, below any overflow path

The critical one is the alarm. On a single-pump station the alarm sits above the one start level. On duplex it must sit above the point where both pumps are already running — because that is the only condition that means the station is genuinely losing.

An alarm set below the lag pump start will sound every time the second pump cuts in, which trains everyone to ignore it. That is worse than no alarm.


Step 6: Confirm the arrangement details

These do not change the numbers but they decide whether the station is serviceable.

ItemWhat to confirm
Isolation valvesOne per pump, so either can be removed while the other works
Non-return valvesOne per pump — a shared valve lets the running pump push water back through the idle one
Guide rails or fixed couplingWhether pumps can be lifted out without entering the tank
Control panelAlternating function, and whether it is included or separate
Level controlTwo independent switch sets, or a combined multi-level arrangement
VentilationSized for the larger tank

The non-return valve point catches people out. With two pumps on one discharge header, each needs its own non-return valve. Without it, the running pump discharges backwards through the idle pump and back into the tank — the station appears to run constantly and moves very little.


Worked example

A small guest house: six en-suite rooms plus a communal kitchen, all below sewer level.

StepValueNote
Duty flow9 m³/hPeak from six showers plus kitchen
Total head7 m4.5 m static, 2.5 m friction over 30 m of 50 mm pipe
Pump specificationTwo pumps, each 9 m³/h at 7 mFull duty each, not half
Working volume240 LSingle-pump equivalent ~170 L, increased for duplex
Stop level150 mm above tank floorKeeps both pumps submerged
Lead start240 L above stop
Lag start300 L above stop
High-level alarm360 L above stopAbove both-pumps running level
IsolationOne valve per pumpService without shutdown
Non-returnOne per pumpPrevents backflow through idle pump

The numbers themselves are less important than the order: duty first, then pumps at full duty, then volume, then levels.


Common sizing errors

ErrorConsequence
Two pumps at half dutyStation falls behind whenever one pump is out
Same tank volume as single-pumpBoth pumps short-cycle
Alarm below lag startAlarm sounds routinely and gets ignored
One non-return valve sharedRunning pump recirculates through the idle one
No isolation valvesCannot service a pump without draining the tank
No alternating controlOne pump does all the work; standby is untested
Sizing on average inflowStation runs continuously at peak

Working on a real project?

Send the fixture list, not the model code

Send the fixture list, required lift height and supply voltage. We will recommend the matching model from the 2026 catalog.

FAQ

Do both pumps need to be the same size? Yes, in almost all cases. Unequal pumps complicate the control logic and the alternating function, and the smaller pump cannot serve as standby for the larger duty.

Can both pumps run at the same time? Yes, briefly, and that is useful for genuine peaks. It should not be the basis for sizing — the station must perform on one pump.

How much bigger is the tank than a single-pump version? Roughly 1.3 to 1.5 times the working volume, depending on how much of a step you set between lead and lag start levels.

What is the minimum number of level switches for duplex? Two start levels, one stop level and one alarm — four distinct levels. Some controllers achieve this with fewer physical switches by using a multi-level float or an electronic probe.


Next step

Send the fixtures served, the vertical lift and the discharge route, and we will confirm the pump duty, the working volume and the four level settings for a duplex arrangement — or tell you if the installation is better served by a single pump with a high-level alarm.

Request a quotation · Single vs duplex stations · See the range


Still unsure? Message the engineer on WhatsApp.

Models referenced in this note