The Fixture Unit Method for Sizing Lifting Devices

2026-11-055 min readSelection Guide

Fixture units express different outlets on a common scale so peak flow can be estimated before anything is built. How the method works and where it breaks down.

The fixture unit method assigns each type of outlet a number representing how much it loads the drainage system, then combines those numbers to estimate the peak flow a station must handle. A WC scores higher than a basin because it discharges more, faster. Add up the units, apply the diversity factor for the building type, and you have a design flow — without measuring anything, and before the building exists.

It is the standard approach in European drainage design, and it is the reason a sizing calculation can be done from a floor plan rather than from a flow meter.


Why a common scale is needed

You cannot simply add up the flow rates of every outlet, because they never all run at once. A building with twenty basins does not produce twenty times a single basin's flow — most are idle at any moment.

The fixture unit method solves two problems at once:

  1. It puts different outlet types on one scale, so a WC and a shower can be added together.
  2. It applies a diversity factor, so the total reflects realistic simultaneous use rather than theoretical maximum.

The result is a design flow that is deliberately higher than average use and lower than everything running at once.


Indicative discharge units

The values below follow the European approach set out in BS EN 12056-2. Local codes may modify them, and you should use the figures that apply in your market — but the relative weightings are consistent.

OutletIndicative discharge units (DU)
Wash basin, bidet0.5
Shower0.6
Bath0.8
Kitchen sink0.8
Washing machine (domestic)0.8
WC, 6 litre cistern2.0
WC, 9 litre cistern2.5
Urinal0.5

Two things stand out. A WC carries four times the load of a basin, which is why a bathroom is dominated by its toilet. And a washing machine is not trivial — it discharges at its own pump rate at the end of a cycle, which frequently coincides with other use.


Applying the diversity factor

The sum of the units is converted to a design flow using a relationship of the form:

Q = K × √(ΣDU)

The square root is the diversity. Doubling the number of outlets does not double the flow; it multiplies it by about 1.41. That reflects the reality that not everything runs together.

K is a factor that depends on how the building is used. Intermittent domestic use has a lower K than a building where fixtures are in near-constant use, such as a public toilet block or a restaurant. The applicable K values are set by the code in force — check them rather than assuming.

The practical effect: a domestic bathroom and a public restroom with the same total DU do not have the same design flow. The public one is used more continuously, so its K is higher.


A worked example

A basement drainage with one WC, one basin, one shower and one washing machine.

OutletDU
WC (6 L)2.0
Basin0.5
Shower0.6
Washing machine0.8
ΣDU3.9

Square root of 3.9 ≈ 1.97.

With a domestic K of 0.5, the design flow is approximately 1.0 L/s. With a K of 1.0, as might apply in a busier setting, it is approximately 2.0 L/s.

That range — 1.0 to 2.0 L/s, or roughly 60 to 120 L/min — is the number the pump has to handle, and it is the number that goes into the pump curve alongside the total dynamic head.

Note what the calculation has done: it has turned a list of fixtures into a flow rate without any measurement, and it has made the effect of the washing machine visible — remove it and ΣDU drops to 3.1, which changes the design flow by around 11%.


Where the method breaks down

The fixture unit method is a design tool, not a measurement. It has limits worth knowing.

It assumes typical discharge patterns. A fixture that discharges unusually — a large bath emptied quickly, an industrial appliance — may exceed what its unit value suggests.

It does not account for pumped discharge. A washing machine or dishwasher discharging under its own pump delivers flow at a rate set by that pump, not by gravity. On a small station this can dominate the peak.

It does not account for infiltration. Groundwater entering a buried tank or a damaged pipe adds flow that no fixture list predicts.

It does not size the tank. The method gives you a flow, not a volume. Tank sizing is a separate question — see how to choose tank volume.

Codes differ. The unit values and the K factors vary between jurisdictions. A calculation done to one code and applied in another market is a source of error.


From design flow to a model

Once you have the design flow and the total dynamic head, the selection is a matter of finding the duty point on the curve.

Two checks before committing:

  • Is the design flow within the pump's range at your head? A pump rated for a higher maximum flow may deliver much less at the head you actually have.
  • Does the tank buffer the peak? If a bath empties faster than the pump can move it, the tank has to absorb the difference. That is a volume question, not a pump question.

Working on a real project?

Send the fixture list, not the model code

Send the fixture list, required lift height and supply voltage. We will recommend the matching model from the 2026 catalog.

FAQ

What is a fixture unit? A number representing the drainage load of one outlet relative to others, used to estimate peak flow without measuring it. A WC is typically around 2 units, a basin around 0.5.

Why is the square root used? Because not all fixtures run simultaneously. The square root relationship applies a diversity factor, so adding fixtures increases the design flow less than proportionally.

Can I just add up flow rates instead? Only if you know the simultaneous flow, which for a domestic installation you usually do not. The fixture unit method gives a defensible estimate from a floor plan.

Does the method work for commercial buildings? Yes, but the diversity factor changes. Buildings in near-continuous use have a higher factor than domestic dwellings, which raises the design flow for the same total units.