A non-return valve allows flow one way and blocks it the other. The five types, which ones suit a lifting station, and the four ways they fail.
What is a non-return valve
A non-return valve allows flow in one direction and prevents it in the other. It has no handle and no actuator — the flow itself opens it, and the flow stopping closes it.
The other names are worth knowing, because suppliers use them interchangeably: check valve, one-way valve, reflux valve, and in drainage work, backflow preventer. They are the same function with different regional habits.
On a buried lifting station the valve has one specific job: stop the discharge column running back into the chamber when the pump stops. It is a cheap component and its failure causes more damage than its cost suggests.
This article covers why the valve is necessary, the five types, which suit a lifting station, and the four ways they fail.
Why the station needs one
Three consequences follow from not having one, and they escalate.
The pump restarts into a full column. After the pump stops, the discharge pipe is full of sewage. Without a non-return valve that column runs back into the chamber, the level rises immediately, the float calls for the pump again, and the cycle repeats. The result is a station that short-cycles continuously — dozens of starts an hour instead of a handful.
The pump can run backwards. Water flowing back through the pump spins the impeller in reverse. A submersible pump driven backwards can loosen its impeller or damage the seal, and the effect compounds every cycle.
The chamber refills with what it just discharged. The sewage returns, and so does everything the pump was clearing. In a station with a long discharge run, the returning volume can be most of what was pumped.
There is also a fourth consequence in a duplex station: without a valve on each pump, one pump discharges back through the other. See Installing a duplex pump station.
The five types
| Type | How it works | Characteristics |
|---|---|---|
| Swing check | A hinged disc swings open with flow and closes on reverse | Simple, low resistance, needs horizontal or specific orientation |
| Lift check | A disc lifts off a seat with flow and drops back | Compact, works in any orientation, higher resistance |
| Double disc (wafer) | Two spring-loaded half-discs | Compact, short face-to-face, common in larger pipework |
| Ball check | A ball seats against a ring on reverse | Tolerant of solids, simple, used in drainage |
| Diaphragm / duckbill | A flexible element that collapses one way and seals the other | Excellent for solids, low cost, limited pressure rating |
Which suits a lifting station
For a small packaged station, the usual choice is a ball check or a swing check built into the discharge assembly, often combined with the isolation valve in a single fitting.
Two reasons: solids tolerance and orientation flexibility. A sewage discharge carries material that will hold a swing disc open if it lodges under the seat, and a valve that cannot close properly is worse than no valve at all — it gives the illusion of protection while allowing backflow.
A spring-assisted valve closes faster and reduces the backflow volume, at the cost of some head loss and a spring that can become fouled.
Where it goes
The valve belongs on the discharge, downstream of the pump and upstream of the isolation valve, so that the isolation valve can be closed to service the pump without the discharge column draining back through it.
That arrangement gives, in order from the pump: pump → non-return valve → isolation valve → discharge.
The order matters. Reversed, the isolation valve traps the column above the non-return valve, and closing it does not let the pump be removed without the column draining into the chamber anyway.
See Where to fit the non-return valve and Non-return valve and isolation valve: do you need both.
The four failure modes
1. Not seating
The most common. The valve closes but does not seal, so the discharge column leaks back slowly.
Symptoms: the pump restarts periodically with no inflow to justify it; the start count climbs; a running or gurgling sound at the discharge after the pump stops.
Causes: debris on the seat, wear on the sealing face, a distorted disc, a spring that has lost tension, or a valve installed in the wrong orientation.
See Non-return valve not sealing.
2. Stuck open
The valve does not close at all. Usually a solid lodged under the disc or in the hinge.
Symptoms: identical to a leaking valve but faster — the chamber refills almost completely after each cycle.
3. Stuck closed
Less common, and more obvious: the pump runs, the discharge pipe is pressurised, and no flow arrives at the far end. The pump may sound loaded, and the current will be high.
Causes: scale, hardened grease, a failed spring, or a valve fitted against the flow direction.
4. Water hammer
A valve that closes instantly on a moving column produces a pressure surge. The symptom is a bang at the moment the pump stops, and the consequence is damage to pipework, fittings and the valve itself.
Spring-assisted valves close more slowly and reduce this. Where the discharge run is long or the flow velocity is high, water hammer is a design consideration rather than a nuisance.
Non-return valve and isolation valve are not the same thing
They are constantly confused, and the confusion leads to installations with one where there should be two.
| Non-return valve | Isolation valve | |
|---|---|---|
| Operated by | Flow | A handle |
| Function | Prevents reverse flow | Allows flow to be shut off |
| Normal position | Automatic | Open |
| Used for | Protecting the pump and the chamber | Servicing the pump |
A non-return valve cannot be used to isolate a pump for maintenance — it holds against reverse flow, not against forward pressure from the discharge side. An isolation valve cannot substitute for a non-return valve because nobody will be there to close it when the pump stops.
Both are needed, and the station needs both. See Non-return valve and isolation valve: do you need both.
What to specify
Four parameters decide whether a given valve suits the duty.
Nominal size. Matched to the discharge pipe. An undersized valve adds head loss; an oversized one may not have enough flow to open fully.
Pressure rating. Above the maximum head the pump can generate, with margin for surge.
Material. The body, the seat and the sealing element all have to survive sewage. Cast iron bodies with elastomer seats are common; some plastics are attacked by fats and solvents.
Solids tolerance. The decisive parameter for sewage. A valve with a narrow seat and a small clearance will hold debris and stop sealing, which is why ball and diaphragm types are favoured where solids are present.
A fifth consideration: serviceability. A valve that cannot be opened for cleaning will be replaced rather than cleaned, and on a sewage duty it will need cleaning.
Working on a real project?
Send the fixture list, not the model code
Send the fixture list, required lift height and supply voltage. We will recommend the matching model from the 2026 catalog.
FAQ
What is the difference between a non-return valve and a check valve? None in function. They are different names for the same device, used in different regions and industries.
Why does a lifting station need a non-return valve? Without one, the discharge column runs back into the chamber every time the pump stops. The station then short-cycles, the pump can run backwards, and the chamber refills with what was just pumped out.
Where should the non-return valve be fitted? On the discharge, downstream of the pump and upstream of the isolation valve, so the pump can be serviced without the discharge column draining back.
Can I use an isolation valve instead? No. An isolation valve is manual and would have to be closed every time the pump stopped. A non-return valve operates automatically on flow.
How do I know if my non-return valve is failing? The pump restarts when there is no inflow, the start count rises, or you can hear water running back after the pump stops. All three point to the same component.
Next step
Tell us the discharge size, the pump head, the pipe run and what the station receives. We will tell you which valve type suits the duty, where it should sit in the assembly, and whether the discharge run needs anything else.
Request a quotation · See the range · Where to fit the non-return valve
Related reading
- Where to fit the non-return valve — position and orientation
- Non-return valve not sealing — the most common failure
- Non-return valve and isolation valve: do you need both — the confusion resolved
- How to fit a non-return valve on a vertical discharge — the vertical case
- Sewage pump short cycling — the symptom a failing valve produces