Non-Return Valve on a Vertical Discharge

2026-11-056 min readInstallation and Commissioning

A vertical riser is the hardest place for a non-return valve to work. Flap valves will not seat, the static head is at maximum, and access is worst. What to fit and where.

A vertical discharge is the hardest place to make a non-return valve work. Three things change when the pipe runs upward:

  • Gravity now works against the valve. A flap that closes by its own weight on a horizontal run will hang open on a vertical one.
  • The static head is at its maximum at the valve. The full weight of the riser column sits on the seat, every time the pump stops.
  • Access is worst. The valve is usually behind the pump, above the floor, in a chamber.

Get the valve type and its position right and the riser works for decades. Get either wrong and the station backflows from the day it is commissioned.


Which valve type works on a vertical riser

TypeWorks on vertical upflow?Notes
Swing / flap checkOnly if the hinge is at the topThe flap must fall closed. Horizontal-only versions will not seat.
Spring-loaded checkYesThe spring closes the valve regardless of orientation. Best general choice.
Ball checkYesThe ball seats by buoyancy and pressure. Good with solids, but can chatter.
Dual-plate (wafer) checkYes, with careLow head loss, but the plates must be specified for vertical flow.
Lift checkYesReliable, higher head loss, needs straight pipe either side.
Butterfly with actuatorYesMotorised, positive closure, needs power and control.

For a domestic or light commercial lifting station on a vertical riser, a spring-loaded check or a ball check is the practical answer. Both close against gravity by design rather than relying on the flap falling.

A swing check can be used if — and only if — it is a vertical-flow version with the hinge at the top so the flap swings down to close. A horizontal-flow swing check fitted into a vertical pipe will hang open and the station will backflow.


Where to fit it

The order on the riser, from the pump upward:

  1. Pump outlet
  2. Non-return valve — as close to the pump as practical
  3. Isolation valve
  4. Union or flange for maintenance access
  5. Riser to the discharge point

Why the non-return valve goes below the isolation valve: if the isolation valve is above it, you can close the valve and still have the valve protected from the column while you service the pump. If the order is reversed, closing the isolation valve leaves the non-return valve under the full static head with no way to release it.

Why as close to the pump as practical: every metre of pipe between the pump and the valve is a metre that drains back into the tank when the valve fails. Keeping that distance short limits the volume of the return.

Why you need a union: a non-return valve is a serviceable item. If it is buried between two solvent-welded fittings, the only way to replace it is to cut the pipe.

The general principles are covered in where to fit a non-return valve.


The static head problem

On a vertical riser, the pressure at the non-return valve when the pump stops is the full height of the column above it. A 5 m riser of 50 mm bore holds about 10 litres, and the pressure at the valve is roughly 0.5 bar. A 10 m riser is 1 bar.

Two consequences:

The valve must be rated for the static head, not just the pump's discharge pressure. Most plastic-bodied valves are rated well above domestic heads, but check before fitting. A valve that deforms under static load will not seat.

The closure is abrupt. A column of water falling back against a suddenly closed valve produces a pressure spike — water hammer — that can be several times the static head. On a tall riser, this is audible as a bang and it is what eventually cracks fittings.

Riser heightMitigation
Under 3 mSpring check is usually sufficient
3–8 mSpring check with a slow-closing characteristic, or a ball check
Over 8 mConsider an air vessel or a surge arrestor above the valve

If you hear a bang on every pump stop, the closure is too fast for the head. Do not ignore it — it is loading every joint in the riser.


Step by step

Before you start: isolate the power, close the inlet, pump the tank down, and confirm the riser is empty. A riser full of sewage released by removing a fitting is the classic accident on this job.

  1. Confirm the flow direction. The arrow on the valve body points away from the pump, in the direction of flow. This is the single most common installation error.
  2. Check the valve is the right type for vertical flow. Not a horizontal swing check.
  3. Dry-fit the assembly — valve, isolation valve and union — and confirm the total height fits the available space.
  4. Support the pipe. A vertical riser with valves in it needs a pipe clip above and below the assembly. The valves should not carry the weight of the pipe.
  5. Fit the valve with the correct gaskets or thread sealant for the pipe material.
  6. Fit the isolation valve above it.
  7. Fit the union for future access.
  8. Pressure test the assembly before refilling the tank, if the arrangement allows.
  9. Refill and run one cycle. Listen at the valve as the pump stops.
  10. Check for return flow. Mark the tank level after the pump stops and check again in ten minutes.

What "not seating" looks like

SymptomLikely cause
Tank level rises steadily after the pump stopsValve held open by debris, or wrong type for vertical flow
Audible trickle in the riserSeat damaged or scaled
Bang on every stopClosure too fast for the head, or a swing check slamming
Backflow only after a few monthsScale or solids on the seat
Backflow only when the tank is fullStatic head overcoming a weak spring
No backflow but reduced flowValve undersized, or a lift check adding head loss

The first and last are the two that get misdiagnosed. A rising tank level after the pump stops is a valve problem, not a pump problem. Reduced flow with no backflow is usually an undersized valve body.


Maintenance

TaskInterval
Listen at the valve after the pump stopsMonthly
Strip and clean the valveAnnually
Replace the seat or the whole valveEvery 5 years, or at any sign of backflow
Check pipe supports above and belowAnnually
Check for water hammerAt every service

The annual strip and clean is what prevents the callout. A valve that is cleaned on schedule rarely fails; one that is never touched fails on the piece of debris that arrives in year four.


Working on a real project?

Send the fixture list, not the model code

Send the fixture list, required lift height and supply voltage. We will recommend the matching model from the 2026 catalog.

FAQ

Can I use a swing check valve on a vertical pipe? Only a vertical-flow version with the hinge at the top, so the flap falls closed. A horizontal-flow swing check fitted vertically will hang open and the station will backflow.

Where should the non-return valve go — above or below the isolation valve? Below it, close to the pump outlet. That way closing the isolation valve protects the pump, and the non-return valve is not left under full static head with no release.

Why does my pipe bang when the pump stops? Water hammer. The column falling back closes the valve abruptly, and the pressure spike loads every joint. On a tall riser, use a slow-closing or spring-assisted valve, or add a surge arrestor.

Does the non-return valve affect pump performance? It adds head loss, which is why the valve body should not be smaller than the discharge pipe. An undersized valve reduces flow and pushes the pump off its duty point.


Next step

If the riser keeps backflowing or banging, send the riser height, the pipe bore and the valve type currently fitted. We will confirm the right valve and the correct position in the assembly.

Request a quotation · Where to fit a non-return valve · See the range