Gravity works whenever the drain can fall to the sewer. When it cannot, you pump. The four measurements that decide it, and the running cost you take on when you pump.
The decision is not a matter of preference. Water falls if it can, and it can whenever there is enough height between the fixture outlet and the point of connection. If there is not, you pump.
Everything else — cost, maintenance, noise, failure modes — follows from which side of that line the installation sits on.
The four measurements that decide it
You need four numbers before you can answer the question. None of them is a guess.
| Measurement | What it is | Why it decides |
|---|---|---|
| Invert level of the connection | The height of the bottom of the sewer or drain pipe you are connecting to | This is the target the water has to reach |
| Fixture outlet level | The height of the lowest drain being served | This is where the water starts |
| Horizontal run | The developed length from fixture to connection | Sets the fall required |
| Available fall | The difference between the two levels, minus the pipe diameter | Compared against the fall required |
The test: available fall ≥ required fall. If it is, gravity works. If it is not, you pump.
Required fall is normally expressed as a gradient — a common figure for a 110 mm drain is around 1 in 60 to 1 in 80, and steeper for smaller pipes. The exact figure for your installation comes from local regulations, not from a rule of thumb.
The calculation, plainly
Suppose a basement bathroom's lowest outlet is 300 mm above the floor slab, and the sewer connection invert is 2.2 m below that floor level.
| Item | Value |
|---|---|
| Fixture outlet level | +0.30 m relative to floor |
| Sewer invert level | −2.20 m relative to floor |
| Difference | 2.50 m |
| Horizontal run | 18 m |
| Gradient available | 2.50 ÷ 18 = about 1 in 7.2 |
1 in 7.2 is far steeper than the 1 in 60 needed, so gravity works — but the pipe would have to be laid at a gradient much steeper than normal, which may not be possible in the space. In practice this is the case where you can use gravity but the excavation is deep and expensive.
Now suppose the sewer invert is only 0.1 m below the floor, and the fixture outlet is 0.3 m above the floor, with a 15 m run:
| Item | Value |
|---|---|
| Difference | 0.40 m |
| Horizontal run | 15 m |
| Gradient available | 0.40 ÷ 15 = 1 in 37.5 |
That is workable for a large pipe but marginal for a small one, and there is no room for error. A slightly longer run or a slightly lower outlet and it fails.
When gravity is the right answer
| Condition | Note |
|---|---|
| Sufficient fall available | The calculation above |
| Fixtures at or above sewer level | Ground floor and above, in most cases |
| No need to lift water | Gravity cannot lift, ever |
| Route can be laid at the required gradient | Space and structure allow it |
Gravity is cheaper to install, free to run, silent, and has no moving parts to fail. When it is available, it wins on every measure.
When you have to pump
| Condition | Why |
|---|---|
| Fixtures below the sewer invert | Water has to go up; gravity cannot |
| Fall available but route impossible | Structure, services or a party wall blocks the trench |
| Connection point too high | A raised sewer, or a connection into an existing high-level drain |
| Long run with insufficient gradient | The fall runs out before the connection |
| Remote outbuilding | Discharge must reach a sewer that is higher |
The commonest case is simply a basement. Below the sewer invert, there is no gradient that works, because the water has to travel upwards. That is where a buried lifting station earns its place: it is the only thing in the building that can move water up against gravity.
What pumping costs you over gravity
This is the honest part of the comparison. Pumping is not just a purchase price — it is a set of ongoing obligations.
| Cost | Detail |
|---|---|
| Purchase and installation | Pump, tank, controls, discharge pipe, electrical supply |
| Running cost | Electricity for every litre lifted, for the life of the installation |
| Maintenance | Blockages, float checks, seal wear, alarm tests |
| Failure risk | A pump can fail; gravity cannot |
| Noise | A pump is audible inside the building; gravity is silent |
| Space | A tank has to go somewhere |
| Power dependency | No power, no drainage — needs a plan |
The power dependency is the one people forget. A gravity drain works during a power cut. A pumped installation does not, and the tank fills. On a basement bathroom that is a small inconvenience; on a basement flat it is a flood risk. Plan for it: a high-level alarm at minimum, and a decision about what happens next.
The middle option: pump to a gravity drain
There is a third arrangement that is often the best answer, and it is worth naming separately.
| Arrangement | Description |
|---|---|
| Full gravity | Fixtures fall to the sewer throughout |
| Pump then gravity | Fixtures fall to a collecting tank, the pump lifts to a high-level gravity drain, which then falls to the sewer |
| Full pumped | The pump lifts all the way to the connection |
The middle option is common and often cheaper to run than full pumping, because the pump only lifts to the nearest available gravity drain rather than to the sewer. It also means a shorter discharge run and lower head.
Ask whether a gravity drain exists within reach before accepting a full pumped design. Sometimes the nearest suitable drain is a soil stack on the floor above, and lifting 2 m is much cheaper than lifting 4 m over 30 m.
Comparison table
| Criterion | Gravity | Pumped |
|---|---|---|
| Capital cost | Lower | Higher |
| Running cost | None | Electricity per litre |
| Reliability | Very high — no moving parts | Depends on pump and controls |
| Works in a power cut | Yes | No |
| Noise | None | Audible |
| Maintenance | Occasional rodding | Regular checks |
| Can lift water | No | Yes |
| Space needed | Pipe route only | Tank plus pipe route |
| Suits a basement | Only if the sewer is lower still | Normally the only option |
Working on a real project?
Send the fixture list, not the model code
Send the fixture list, required lift height and supply voltage. We will recommend the matching model from the 2026 catalog.
FAQ
Can I use gravity drainage from a basement? Only if the sewer connection is lower than the basement floor, which is unusual. In most basements the sewer is above the floor level, so the water has to be lifted.
How much fall does a drain need? It depends on the pipe diameter and the local regulations. A common figure for a 110 mm drain is around 1 in 60 to 1 in 80. Do not use a rule of thumb in place of the applicable standard.
Is pumped drainage allowed for a habitable basement? Usually yes, subject to building regulations in your area, and often with requirements for an alarm and sometimes for a standby pump. Check the local requirements before designing.
What happens to a pumped system in a power cut? The tank fills. Nothing can be drained until power returns. This is why a high-level alarm matters, and why some installations specify a standby supply.
Next step
Send the fixture outlet level, the sewer invert level and the horizontal run, and we will tell you whether gravity is available, whether a short lift to a nearby drain would work, or whether the installation needs a full pumped solution — and what that costs you in running terms.
Request a quotation · Pumping sewage uphill · See the range
Related reading
- Pumping sewage uphill when gravity drainage is impossible — the case where you must pump
- Minimum fall for drainage into a lifting station — the inlet side
- Calculate total dynamic head — how much lift you actually need
- Sewage pump vs sump pump — choosing the pump once you have decided to pump
- Basement bathroom without gravity drainage — the commonest case in detail
- Lifting station for a garage or workshop — a duty that almost never has a gravity option