Sometimes — provided the stack is a true vent running to outside air at full bore. What the connection must satisfy, and when an independent vent is the safer answer.
Yes, in many installations a lifting station can share a vent stack with the building's drainage system — provided the stack is a genuine vented stack that terminates in outside air at full bore, and the connection is taken above the highest fixture connection on that stack. What it must never do is connect into a stack that terminates in an air admittance valve, or into a pipe that is acting as a drain only.
The distinction sounds technical but the consequence is simple: if the stack has a real path to outside air, the station's gas leaves through it. If it does not, the gas has nowhere to go and will find a way into the room.
What the stack must be
Four conditions, all of which must hold.
| Condition | Why |
|---|---|
| Terminates in outside air | Gas must have somewhere to go |
| Full bore to the terminal | A reduced or blocked stack cannot vent |
| No air admittance valve at the top | An AAV admits air but does not release gas |
| Connected above the highest fixture on that stack | Otherwise the station vent can act as a drain, and water can enter it |
The third condition is the one that catches people out. Air admittance valves are common on drainage systems, and a stack fitted with one looks like a vent from the inside of the building. It is not — it is a one-way device that lets air in and holds gas in.
If you cannot confirm what is at the top of the stack, run an independent vent.
Why the connection point matters
Connecting above the highest fixture ensures two things:
- The station vent does not become a drain. If the connection is below a fixture, water from that fixture can enter the vent pipe and run down into the tank.
- The vent does not siphon a trap. A connection placed where the stack is under pressure can pull water out of a trap, which then leaks gas into the room — a problem that looks like a station fault and is not.
The general rule is to connect as high as practical on the stack, and always above the highest fixture connection.
Sizing the shared vent
The station's vent connection must be run at full bore to the stack. Do not:
- Reduce the diameter to make the route easier.
- Run a long horizontal section with a dip where condensate lifting pump collects.
- Use a smaller pipe because the stack is large. The station's vent is sized for the station, and the stack's size is irrelevant to that.
Where the station vent joins the stack, the joint must be a proper drainage fitting, sealed, and accessible for inspection if the code requires it.
For the full venting requirements, see how to vent a sewage lifting station.
When an independent vent is the safer answer
Sharing is convenient and often perfectly adequate. An independent vent is the better choice in these situations:
| Situation | Why independent |
|---|---|
| The stack's termination is unknown or inaccessible | Cannot confirm it is a true vent |
| The stack terminates in an AAV | It will not release gas |
| The station is far from the stack | A long shared run adds friction and condensate traps |
| The building is being refurbished anyway | The marginal cost of a separate vent is low |
| The station serves commercial or high-traffic fixtures | More gas production; more margin is worth having |
| Local code requires it | Some jurisdictions require a dedicated vent for pumped installations |
The cost of an independent vent is a length of pipe and a terminal. The cost of a shared vent that does not work is a smell you cannot diagnose without opening ceilings.
Common mistakes
1. Connecting to an AAV-terminated stack. The most frequent and most consequential. Gas has no exit.
2. Connecting below the highest fixture. Water enters the vent and drains into the tank.
3. Reducing the station vent to match a smaller stack connection. The station's vent is sized for the station.
4. Running the shared vent horizontally with a dip. Condensate closes the pipe within a season.
5. Assuming a large stack means adequate venting. A large stack that is partly blocked vents no better than a small one.
6. Using the discharge pipe as a vent path. The non-return valve closes; there is no vent.
How to check an existing shared vent
If a station is already installed and smells despite having a vent connection, check the shared path before blaming the station.
| Check | How |
|---|---|
| Stack termination | Get to the roof or the external wall and look |
| AAV present? | If yes, the stack is not a vent |
| Blockage | Look for nests, screens packed with debris, frost damage |
| Connection height | Is it above the highest fixture? |
| Reduction | Has the station vent been necked down anywhere? |
| Dips | Trace the horizontal sections |
| Trap siphonage | Are any traps empty after a flush? |
That list resolves most "the vent is fine but it still smells" cases. If all seven check out, the cause is elsewhere — see why a lifting station smells.
Working on a real project?
Send the fixture list, not the model code
Send the fixture list, required lift height and supply voltage. We will recommend the matching model from the 2026 catalog.
FAQ
Can a lifting station share the house vent stack? Yes, if the stack is a genuine vent terminating in outside air at full bore, and the connection is above the highest fixture on that stack.
Can it connect to a stack with an air admittance valve? No. An AAV admits air but does not release gas, so the station's gas has no exit.
Does the station vent need to be the same size as the stack? No. The station vent is sized for the station and run at full bore to the stack. The stack's size does not change the requirement.
What if I cannot find where the stack terminates? Run an independent vent. An unverified shared vent is not worth the risk of an odour problem you cannot diagnose.
Next step
If you are specifying a station, tell us the building layout and where the vent can run. We will confirm the vent connection size for the model and whether a shared stack connection is appropriate.