Below-sewer fixtures cannot drain by gravity. Learn the backflow-loop geometry, what EN 12050 and EN 12056-4 specify, and how to size the lifting pump.
A basement fixture below the invert of the municipal gravity sewer cannot drain by gravity. Any branch whose outlet is higher than its inlet will back up. The fix needs two things working together: a lifting station to raise the wastewater above the connection point, and a geometric backflow arrangement that stops sewer water from reversing when the main surcharges.
Why gravity drainage fails below the sewer invert
The invert is the lowest point inside a pipe. A gravity main falls downstream under its own weight. A basement toilet, shower or sink below that main has no downhill path: the branch fills to the main's level and stops, and continued use raises the water level in the room.
Two problems follow. First, the wastewater needs energy to reach a higher point: a sealed collection chamber receives the fixture drains and a pump discharges under pressure to the sewer. Second, outside the building, the main can surcharge in heavy rain or a blockage, rising above its invert and sometimes above street level. Without protection, that water finds the lowest open outlet and flows back into the basement.
They need different fixes: a correctly sized pump does not stop a surcharge, and a backwater valve does not lift water. The geometry of the discharge pipe is the element most often under-designed.
What the EN standards actually specify
The EN family separates product type from installation practice.
EN 12050-1 covers lifting devices for wastewater containing fecal matter — blackwater from toilets — including mechanical design, gas tightness and sealing. EN 12050-2 covers wastewater without fecal matter, such as basin, shower and laundry water. EN 12050-3 addresses limited-use lifting devices for fecal wastewater, typically compact units for a single fixture or an occasional-use room. EN 12050-4 deals with check valves used with these devices. These documents define the design requirements for a given duty; they do not state that any particular product meets them.
Installation sits in EN 12056-4. The collecting chamber must be gas- and odor-tight, able to withstand the pressures it may see, and fixed against uplift and rotation — a light, empty tank can try to float. Surface water must not enter an indoor sewage lifting station; rainwater belongs in a separate system. EN 12056-4 calls for at least 60 cm of clear working space around the unit so the pump, valves and controls can be serviced. It also expects a vent connection, taken above the roof or into the building vent system, so pressure cannot build and water seals are protected. Designers use these clauses to set clearances, fixings, vent size and pipe routes.
Designing the anti-backflow geometry
A check valve is necessary but not a complete answer: its disc or flap can be held open by fibers, grit and grease, giving a surcharged main a direct path back. Protection for a below-sewer discharge must be built into the pipe geometry as well as the valve.
The arrangement is a raised loop, or goose-neck: the discharge rises from the pump, passes over a crown above the local backflow level, then falls by gravity to the sewer. If the main surcharges, water in the rising leg cannot cross the higher crown, so an air break is preserved even if the check valve leaks.
In geometric terms: the outlet carries a non-return valve and an isolation valve; the rising main runs vertically to the crown; the crown sits above the street or backflow level with a margin, commonly around 100 mm; the gravity leg falls to the sewer; and the chamber vent goes to roof level or the building vent system. The crown is also the head-calculation reference. Set it too low and the pipe may look acceptable at the wall while offering no real protection.
Sizing hydraulics: TDH and self-cleaning velocity
The pump must deliver the design flow against the full resistance of the system, expressed as total dynamic head (TDH):
TDH = H_geo + H_V,A + H_V,R
The three terms describe different losses. H_geo is the geodetic, or static, head — the vertical distance from the pump stop level to the discharge point. For a below-sewer installation, measure to the highest point of the backflow loop, not merely to the sewer inlet; the crown usually controls, so loop geometry and pump selection cannot be separated. H_V,A is the local loss from bends, tees, valves and the check valve, each expressed through its loss coefficient and flow velocity. H_V,R is the linear friction loss, which grows with run length and the square of flow. Evaluate all three at the same design flow.
Flow velocity matters as much as head. Common design guidance puts minimum self-cleaning velocity at 0.7 m/s in horizontal pipes and 1.0 m/s in risers, with an upper bound around 3.0 m/s. These are design targets rather than mandatory clauses of EN 12056-4. Below the lower values solids settle; above the upper value the system wastes head and becomes noisy. Check velocity at the actual design flow and keep the bore large enough that the threshold is met at part load as well as full flow.
Anteloy AT series selection
The AT range offers compact lifting units in two electrical versions: the A series for 220–240 V, 50 Hz and the B series for 110 V, 60 Hz. Match the supply first.
| Model | Power input (P1) | Maximum flow | Maximum head | Protection class | Voltage | Start level | Stop level |
|---|---|---|---|---|---|---|---|
| AT-C300A | 300 W | 100 L/min | 6.5 m | IP54 | 220–240 V, 50 Hz | 55 mm | 25 mm |
| AT-C450A | 450 W | 125 L/min | 8 m | IP55 | 220–240 V, 50 Hz | 75 mm | 35 mm |
| AT-C600A | 600 W | 150 L/min | 9.5 m | IP55 | 220–240 V, 50 Hz | 65 mm | 35 mm |
| AT-C750A | 750 W | 165 L/min | 11 m | IP55 | 220–240 V, 50 Hz | 65 mm | 35 mm |
| Model | Power input (P1) | Maximum flow | Maximum head | Protection class | Voltage | Start level | Stop level |
|---|---|---|---|---|---|---|---|
| AT-N300B | 300 W | 85 L/min | 6 m | IP54 | 110 V, 60 Hz | — | — |
| AT-N450B | 450 W | 115 L/min | 8 m | IP55 | 110 V, 60 Hz | 75 mm | 35 mm |
| AT-N600B | 600 W | 130 L/min | 9 m | IP55 | 110 V, 60 Hz | — | — |
| AT-N900B | 900 W | 170 L/min | 12 m | IP55 | 110 V, 60 Hz | — | — |
For the AT-C300A sewage lifting device, Class F insulation and operation below 45 dB are listed values. Where a Start level or Stop level is not shown, confirm the setting against the specific data sheet.
Compare TDH with Maximum head and design flow with Maximum flow, leaving margin for future pipe-run changes. Start level and Stop level set the chamber's working volume and therefore cycling: a narrow band gives short, frequent cycles, a wider band reduces cycling but stores more water. For fecal duty, use a device type appropriate to that duty within the EN 12050 family.
Installation checklist
A field checklist keeps geometry and equipment aligned:
- Confirm the highest point of the discharge loop sits above the street or backflow level, with the intended margin.
- Verify velocity: at least 0.7 m/s in horizontal runs and 1.0 m/s in the riser, at design flow.
- Fit a non-return valve and an isolation valve on the discharge, with the non-return valve accessible.
- Take the chamber vent to roof level or the building vent system; do not terminate it indoors.
- Keep surface water and rainwater separate from the indoor sewage lifting station.
- Confirm the chamber is gas- and odor-tight and fixed against uplift and rotation, with at least 60 cm of clear working space.
To have the lift, pipe run and proposed unit checked against a real layout, send details through the quote form.
Working on a real project?
Send the fixture list, not the model code
Send the fixture list, required lift height and supply voltage. We will recommend the matching model from the 2026 catalog.
FAQ
Q: Can a check valve alone stop sewer backflow into a basement? No. A check valve can be held open by debris. A raised loop with its crown above the backflow level provides a physical air break that works even when the valve leaks; in practice the two are used together.
Q: What is the difference between EN 12050-1 and EN 12050-3? EN 12050-1 covers general lifting devices for fecal wastewater; EN 12050-3 covers limited-use devices, typically compact units for a single fixture or occasional-use room. EN 12050-2 deals with non-fecal water and EN 12050-4 with check valves.
Q: How high should the top of the backflow loop be? Its crown should sit above the local backflow level, normally street level, with a margin — commonly around 100 mm. The crown is also the static-head reference, so fix it before selecting the pump.
Q: How do I choose between the A and B series? Start with the supply: A-series units are rated for 220–240 V, 50 Hz and B-series units 110 V, 60 Hz. Then compare design flow and TDH with Maximum flow and Maximum head, and check Start level and Stop level against the chamber.