Air Lock in a Sewage Lifting System

2026-11-108 min readMaintenance and Troubleshooting

An air lock is a trapped pocket of air that stops the flow. Where it forms, how to tell it from cavitation and lost prime, and how to clear it.

Air lock in a sewage lifting system

An air lock is a pocket of air trapped in pipework or in a pump, in a position where the pump cannot push it out. Because air is compressible and much lighter than sewage, the pump works against a cushion instead of moving liquid, and the flow stops or drops to a trickle.

In a sewage lifting station it happens most often in three situations: at first commissioning, after the station has been drained for maintenance, and on a discharge route with a high point that holds air.

It is often confused with two other problems — lost prime and cavitation — and the three have different causes and different fixes. Getting the diagnosis right is most of the work.


Three faults that look alike

What is happeningWhere it happensDistinguishing sign
Air lockA trapped air pocket blocks the flow pathDischarge pipe at a high point, or inside the pumpPump runs, little or no flow, no unusual noise, clears if air is released
Lost primeThe pump has no liquid in it to moveSuction side of a dry-installed pumpPump runs fast and light, never picks up
CavitationLiquid boils inside the pump because pressure is too lowPump inlet, when suction conditions are poorRattling, gravel-like noise, flow drops under load

The practical difference: an air lock is silent and a cavitation problem is noisy. And an air lock is a plumbing condition, while cavitation is a hydraulic design condition.

An air lock in a submersible station is almost always in the discharge pipe. A submersible pump cannot lose prime, which rules out the second row entirely. See Sewage pump losing prime for that case.


Where air gets trapped

1. The high point of the discharge run. The classic. A discharge route that rises, then falls, then rises again traps air at the first local peak. The pump pushes the air to the top of that peak and cannot push it over.

2. A horizontal run with a slight fall against the flow. Air collects along the top of the pipe and forms a long bubble that the flow cannot shift.

3. A non-return valve installed in the wrong orientation. A valve that needs to be horizontal fitted vertically, or one fitted against the flow arrow, can hold air as well as failing to seal. See Where to fit the non-return valve.

4. Inside the pump, at first commissioning. A new pump that has been stored dry may have air in the volute. Submersible pumps normally clear this within a few seconds of running; a pump that does not may have a blocked or damaged impeller rather than an air lock.

5. A discharge pipe that leaves the chamber above the pump. The vertical section holds air until the flow fills it. Usually clears in one cycle, but on a shallow installation with a short cycle it can persist.

6. A vent or air valve that is blocked. Where an air release valve is fitted, a blocked or seized one converts a self-clearing condition into a permanent air lock.


How it presents

The signature of an air lock is specific, and it is different from a blockage.

The pump runs normally. Current is normal or slightly low — not high, as it would be with a jam. The pump is not straining; it is pushing against a cushion.

Flow is absent, or starts then stops. A common pattern: the pump runs, water moves for a few seconds, then stops while the pump continues. That is the pump pushing the air pocket to a point where it can no longer move it.

No unusual noise. No rattling, no gravel. Just the normal sound of a running pump with nothing happening.

The station may still empty, slowly. If the air pocket is small, some flow gets past and the level falls over a long period rather than stopping entirely.

It often follows maintenance. A station that worked, was drained, and then did not work is an air lock until proven otherwise.


Clearing it

On a station with a high point

Fit or open an air release point at the high point. This is the correct fix and it is a design change, not a workaround. A manual air release valve at the peak lets the pocket out; an automatic one keeps it clear.

Where no release point exists, the practical options are to fill the pipe slowly from the discharge end if the arrangement allows, or to run the pump in short bursts with the discharge partially open so that the air is carried through in stages rather than compressed.

On a new installation

Run the pump and watch the discharge. If the flow establishes within one or two cycles, the air has cleared and no action is needed.

If it does not, check the impeller before assuming an air lock. A blocked impeller on a new installation is more common than a persistent air lock, and the symptoms are similar from outside.

On a station that has been drained

Refill slowly, and let the air out as it fills. A chamber filled quickly pushes air into the discharge pipe in a slug that is hard to shift. A chamber filled at a moderate rate lets the air escape as the level rises.


Why it comes back every time the pump stops

A station that air-locks on every restart has a specific condition: the discharge pipe is draining back after each cycle, and refilling with air.

The component responsible is the non-return valve. If it does not hold, the column of sewage above it runs back into the chamber, and the pipe fills with air. The next start has to push that air out again.

So the sequence is: passing non-return valve → pipe drains back → air enters → air lock on restart. The air lock is the symptom; the valve is the cause.

This is worth checking before anything else on a station with repeat air locks. The test is simple: after the pump stops, listen at the discharge. A running, gurgling sound of water returning means the valve is not seating. See Non-return valve not sealing.


Design decisions that prevent it

DecisionWhat it prevents
Discharge route rising continuously to the connectionThe local high point that traps air
Air release valve at any unavoidable high pointA permanent pocket
Non-return valve in the correct orientationAir held by a wrongly fitted valve
A discharge velocity high enough to carry airLong bubbles along a horizontal run
Avoiding a horizontal run with a fall against the flowAir collecting along the pipe crown
A drain-down point on exposed runsWater left standing that air-locks after freezing

The first row is the one that costs nothing at design stage and is expensive to correct later. A discharge pipe should climb steadily from the pump to the connection point, with no dips and no local peaks. Where the site does not allow that, an air release valve is the answer.


When it is not an air lock

Three conditions that produce the same "pump runs, nothing moves" result:

A blocked impeller. Current is usually high, and the pump may sound loaded. See Sewage pump impeller jammed.

A closed isolation valve. A valve left closed after maintenance is the most embarrassing cause and among the most common. Check it first — it takes ten seconds.

A worn impeller. Flow reduces gradually over months rather than stopping abruptly. See Sewage pump runs but does not pump.

A blocked discharge. The pump runs, the pipe is pressurised, and nothing arrives at the other end. Checking the downstream manhole separates this from an air lock immediately.


Working on a real project?

Send the fixture list, not the model code

Send the fixture list, required lift height and supply voltage. We will recommend the matching model from the 2026 catalog.

FAQ

How do I know if my pump has an air lock? The pump runs normally, the current is normal or low, there is no unusual noise, and little or no water moves. It often follows draining the station or a new installation.

Can a submersible sewage pump air lock? Yes, but in the discharge pipe rather than in the pump. A submersible pump is already submerged, so it cannot lose prime — but the pipe above it can hold air.

Why does my station air lock every time it starts? Because the discharge pipe is draining back after each cycle. The non-return valve is the usual cause, and the air lock is the symptom.

Will an air release valve solve it? At a genuine high point, yes. It will not solve an air lock caused by a passing non-return valve, because that lets air in at the bottom rather than trapping it at the top.

Does an air lock damage the pump? Not directly, but a pump running against a trapped air pocket is running with reduced cooling and no flow. Left long enough, that damages the seal and eventually the winding.


Next step

Tell us the discharge route — the levels, any high points, the length and the diameter — plus whether the air lock happens every start or only after maintenance. We will tell you whether the fix is an air release point, a valve change or a re-route.